1.jpg

1,The wet curtain arrangement should try to reduce the ventilation to ensure indoor ventilation even dead.

2, The design of the wet curtain system should according to the site of summer light and wind consider installing position.

3,The wet curtain adopts embedded type installation, smooth opening around surface treatment and on eaves reserved space for installation.

4, The wet curtain adopts plug-in installation required civil party shall be prefabricated fixings.

5, The wet curtain paper only lateral assembly ,in no case shall avoid impeding the flow of vertical assembly.

6,When the wet curtain with the fan suction  is used ,space ventilation window and other openingsare airtight.

7, The wet curtain with fan positive pressure when in use, the need for a separate design installation scheme according to the construction drawings and use requirements.

8, Water supply is generally appropriate to increase the wet curtain in foundation design of the water supply volume of  drying, high temperature area..

The system use and maintenance

1,The reservoir shall be stamped with the sun and dust, conditional when wet curtain should also do the appropriate shading.

2, When the temperature is below 5 degrees, do not use wet curtain system, avoid impeding airflow, freezing water pipe.

3,When the wet curtain top seal, do not allow the operation of wet curtain system, do not use wet curtain long time should be whole sealing barrier.

4, Befor turning off the water system, the exhaust fan must remain rotating more than 30 minutes till the cooling pad absolutely dry.

5, It should be regularly (weekly) cleaning tank, ensure the cycle water PH keep 6~9and conductivity less than 1000 micromhos.

6, The wet curtain bottom can not have long-term immersion in water in case the algas breeding

 7, When the wet curtain surface algae breeding can put 3 - 5ppm to the pool chlorine or bromine, continuous treatment concentration was 1ppm.

8, The wet curtain operation must ensure the water supply pipe the water evenly, the filter needs cleaning regularly (weekly).

The other explanation

1, The wet curtain paper and wet curtain frame should generally be assembled at the project site, avoid transportation bump.

2, When the size of houses for civil construction error opening party beyond the design error wet curtain scheme, can be fine tuned in assembly.

3, Wet curtain cooling effect  depends on  the performance of the fan , Confined space and Outdoor air humidity.

4,The general should provide the wet curtain system of water pump, electric wire, power distribution boxes and other equipment .

5, the water supply quantity to adjust through the pump selection or valves, visual effect is ideal water for the whole of the wet curtain without the drenched dry streaks, also can see the thin water flowing down along the ripple.

6, Before transported to the construction site for installation, the wet curtain paper shall  kept attention to fire prevention. due to the flammable.

7, Wet curtain system extended change significantly with age.

Wet curtain system based on the correct installation and regular maintenance, the service life of the whole 5 years (artificial damage, transport damage, water quality reasons, other natural disasters except).